In October 2026, networked refrigeration control systems at numerous supermarkets in France became the target of a large-scale cyberattack. Attackers manipulated the system controls and triggered extended defrost cycles. As a result, temperatures rose significantly, cold chains were disrupted, and large quantities of food had to be discarded.
The incident clearly demonstrates the risks associated with the increasing digitalization and connectivity of machines and systems. As connectivity increases, so does the potential attack surface. The consequences of a cyberattack can therefore extend beyond the digital level and have a direct impact on temperatures, pressures, or entire processes. While such an incident in a refrigeration system may primarily result in economic damage, the consequences can be significantly more severe in safety-critical applications.
But what happens when the electronic layer of protection fails?
Cyberattacks are only one of several possible scenarios. Electrical and electronic systems can also be affected by external influences or technical failures. These include electromagnetic interference (EMC), problems with the power supply, or faults in sensors, electronics, and communication systems. Modern systems address such risks with extensive protective measures, diagnostic functions, safety-related control systems, and increasingly, cybersecurity measures. Yet even a comprehensive safety concept cannot cover every conceivable failure scenario.
This is precisely why independent layers of protection are essential. And this brings a technology into focus that may appear almost unspectacular at first glance: mechanics.
A purely mechanical pressure switch requires no software, firmware, IP address, or digital communication interface to perform its switching function. As a result, it has no software-based attack surface of its own and operates independently of digital signal processing. When the pressure reaches a defined limit, the switch responds directly to the physical variable. This technological independence provides an additional layer of protection and can therefore contribute to redundancy within the overall system. Mechanical pressure monitoring does not replace cybersecurity, EMC-compliant design, or electronic safety functions, but instead complements them with a fundamentally different operating principle.
From technological independence to functional safety
Mechanical pressure monitoring can therefore complement existing protective measures with an independent operating principle. This raises another important question: How can this additional layer of protection be assessed within the framework of functional safety?
Safety is not only about preventing attacks and technical failures wherever possible. Equally important is the question of how a hazardous condition can be prevented if other protective measures fail.
This question leads directly to functional safety. The international standard IEC 61508 provides a central framework for this. It defines requirements for safety-related systems and enables the systematic assessment of components intended for use in safety functions. Mechanical components can also be assessed on this basis.
SUCO is therefore currently preparing the certification of its SW24 and SW27 mechanical pressure switch variants in accordance with IEC 61508 for applications up to SIL 3. The planned certification process includes, among other measures, a mechanical Failure Modes, Effects and Diagnostic Analysis (FMEDA). In this way, the planned certification bridges the gap between proven mechanical technology and the safety requirements of tomorrow. As digitalization continues to advance, another characteristic of mechanical pressure switches is gaining importance alongside their robustness: their technological independence.
Technological independence does not mean that mechanical components are free from potential failures or environmental influences. Temperature, vibration, wear, and corrosion can affect them as well. Their strength lies instead in the fact that they are subject to different failure mechanisms and dependencies than digital and electronic systems. The key advantage therefore lies in combining different operating principles. As electrification and digitalization increase, so does the need for additional layers of protection that function independently of electronic and digital systems. Mechanical pressure switches can provide a valuable complement in this context.
With the planned SIL certification of the SW24 and SW27 mechanical pressure switch variants, SUCO aims to make this potential systematically available for safety-related applications in the future. The project is scheduled to start in January 2027 in cooperation with an external certification body.
Especially in an increasingly digitalized world, proven mechanical technology can take on new relevance. The more complex and interconnected systems become, the more valuable a layer of protection can be that is deliberately designed to operate independently of them. When digital systems fail, safety does not necessarily require more digitalization. Sometimes, it requires exactly the opposite: mechanics.